NewModel GDM-100-CV

Gas density monitor

With calibration valve for recalibration

Selected documents
Sales contact

WIKA Instrumentation Corporation (Thailand) Co., Ltd.

Tel.:
+66 2 3266876
Fax:
+66 2 3266874
info@wika.co.th

Applications

  • Medium and high-voltage switchgear
  • Gas density monitoring of SF₆ gas in closed tanks
  • Raising an alarm when defined limit values have been reached

Special features

  • Functional check or recalibration possible without dismounting
  • Case, wetted parts, shut-off valve and test connection from stainless steel
  • Test connection and shut-off valve are welded to prevent leakage

Description

Electrical switch contacts
The gas density, for high-voltage switchgear, is a critical operating parameter. If the requiredgas density is not present, safe operation of the switchgear cannot be guaranteed.

The gas density measuring instruments from WIKA warn reliably against dangerously low gas quantities, even under extreme environmental conditions. Electrical switch contacts warn the switchgear operator if the gas density, on account of a leak, drops below a specified value.

Numerous fields of application
The WIKA gas density monitor is hermetically sealed and temperature compensated. Measured value fluctuations and erroneous alarms caused by changes in either ambient temperature or air pressure are therefore prevented.

Easy and fast functional check
With regard to switchgear safety, asset protection and environmental protection, it is common to perform functional checks on a regular basis. Article 5 of the EU regulation on fluorinated greenhouse gases provides for checking of the leakage detection system at least every 6 years if it contains > 22 kg SF₆ gas and the plant was installed after 01 January 2017.

With the help of the firmly welded calibration valve, the gas density monitor can be shut off from the process and recalibrated without having to disassemble it. This not only reduces maintenance time but also minimises the risks of SF₆ gas emissions and potential leakages during recommissioning.

In order to prevent unintended opening or closing of the shut-off valve, the latter can only be operated using a special tool and a torque spanner. When the shut-off valve is closed, the special tool cannot be removed. The special tool can be removed only after the shut-off valve is opened and the gas density monitor is thus again connected with the switchgear.

Gas density monitor
  • Gas density monitor